ResourcesHSG274 check guide

The routine checks, in one table.

The hot and cold water checks from HSE’s HSG274 Part 2, Table 2.1, as Ecohydro’s templates set them up. They are defaults: your risk assessment sets the frequency for your buildings.

Reading the table

  • Defaults, not rules

    HSG274 says the risk assessment decides how often each check is done. Every template can be changed, with the reason recorded.

  • Rotations

    Representative outlets are checked a few at a time, so every outlet is covered once a year without checking them all each month.

  • Where HSE sets no frequency

    For representative outlets and TMVs the table gives no interval. Our default is marked as ours.

Routine checks from HSG274 Part 2, Table 2.1, as Ecohydro sets them up by default
CheckDefault frequencyTarget
Calorifier flow temperatureMonthlyAt or above 60 °C
Calorifier return temperatureMonthlyNot below 50 °C
Hot water sentinel outletsMonthlyAt least 50 °C within one minute (55 °C in healthcare premises)
Cold water sentinel tapsMonthlyBelow 20 °C within two minutes
Principal loop return temperaturesMonthlyAt least 50 °C (55 °C in healthcare premises)
Subordinate loop return temperaturesQuarterly, on a monthly rotaAt least 50 °C
Hot water representative outletsEach outlet once a year, monthly rota (our default)At least 50 °C (55 °C in healthcare premises)
Cold water representative outletsEach outlet once a year, monthly rota (our default)Below 20 °C
Cold water tank and mains temperaturesYearly, in summerBelow 20 °C
Flush infrequently used outletsWeeklyUntil the temperature stabilises
Clean and descale showers and spray tapsQuarterlyHeads, inserts and hoses clean
Cold water storage tank inspectionYearlyInspected, remedial work where needed
Calorifier inspection and cleanYearlyInspected and cleaned, or debris purged
TMV serviceYearly (our default)Serviced and fails safe, per the manufacturer

Always check the source

This is a summary to help plan routine work. Read HSG274 Part 2 and follow your written scheme and risk assessment.